8 Operation
Maschinenfabrik Reinhausen GmbH 2020136 3587317/21 ENTAPCON
®
Also refer to
2 Setting the switching pulse for controlling the motor-drive unit [►132]
2 Displaying and acknowledging events [►237]
8.11 Regulation
The general functions for regulating the on-load tap-changer are described
in this section.
8.11.1 Response to control system disconnection (optional)
If your device is equipped with a connection to a control system (SCADA),
you can use the following parameters to set how the device is to behave if
the connection to the control system is interrupted.
This function only works in the REMOTE operating mode.
Response to SCADA disconnection No reaction
SCADA disconnection delay time 5s
Figure102: Regulation
1. Go to Settings > Parameters > On-load tap-changer regulator > Regu-
lation.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the Accept button to save the modified parameter.