10 Fault elimination
Maschinenfabrik Reinhausen GmbH 2020278 3587317/21 ENTAPCON
®
Characteristics/details Cause Remedy
Problem with circulating reactive
current minimization parallel oper-
ation method.
Circulating reactive current can-
not be calculated.
Check wiring. Connect as shown in connection
diagram.
Circulating reactive current block-
ing limit exceeded.
Check configuration.
Table123: Parallel operation faults
10.7 Tap position capture incorrect
Characteristics/detail Cause Remedy
Position indicator incorrect.
Leading sign incorrect.
Incorrect wiring. Check wiring.
Connect as shown in connection diagram.
Minimum value of the analog in-
put signal not configured cor-
rectly.
Check parameters.
Position indicator incorrect.
Display fluctuates.
Interference. Shield the line.
Increase distance from source of interference.
Lay interference lines separately.
Route signal in separate lines (filter, shielded
lines).
No position indicator.
"- -" is displayed.
No measurement signal.
No L- for digital input.
Connect signal as shown in connection dia-
gram.
Check wiring.
Connect as shown in connection diagram.
No position indicator.
"?" is displayed.
Bit combination (code) impermis-
sible.
Check wiring.
"Motor running" signal present. Check the signal sequence.
Tap position capture over resistor
contact series faulty.
Faulty calibration. Calibrate tap position capture over resistor con-
tact series.
Modified contact resistance val-
ues of the resistor contact series
(e.g. due to weather or age).
Calibrate tap position capture over resistor con-
tact series.
Table124: Tap position capture
10.8 Assemblies
Consult the following table to check whether individual assemblies have a
malfunction.
Assembly Characteristics/details Cause Remedy
UI 1/UI 3 RDY LED (yellow) does
not light up
No communication with assembly
possible.
Contact Maschinenfabrik Rein-
hausen GmbH.
RDY LED (yellow) flashes An error was detected in the as-
sembly.
Contact Maschinenfabrik Rein-
hausen GmbH.

Table of Contents