8 Operation
Maschinenfabrik Reinhausen GmbH 202092 3587317/21 ENTAPCON
®
Settings
General
Name Value
Language English
Commissioning wizard Yes
Auto-logout Off
Time until auto-logout 15.0min
Measured value display Primary values
Transformer name Transformer
Remote behavior Hardware and SCADA
USB interface Off
Service user access activation Activated
SNMP Agent Off
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin 14.04.2020 14:22
Figure75: General
You must be assigned the administrator role to set parameters.
When in delivery status, you can log in as the administrator as follows:
User name: admin
Password: admin
1. Go to Settings > Parameters > System > General.
2. Select the desired parameter.
3. Set the parameter.
4. Press the Accept button to save the modified parameter.
5. Restart the device to apply the change.
Service user access activation
You can use this parameter to activate or deactivate service user access.
8.3 Configuring the network
You can configure the ETH1 and ETH2.2 network interfaces of the CPU as-
sembly in this menu item.
You can only set the parameters for ETH1 if the device is equipped with the
optional control system connection via Ethernet (TCP/IP):
IEC61850
IEC60870-5-104
Modbus (Modbus type TCP active)
DNP3 (DNP3 transmission type TCP active)
MQTT