8 Operation
Maschinenfabrik Reinhausen GmbH 2020 1273587317/21 EN TAPCON
®
2. Adjust the data points as required.
3. Press the Accept button to adopt the modified list of data points.
4. Restart the device to activate the modified list of data points.
8.8.8.6 Resetting the data point configuration to factory settings
If you want to reset the data point configuration to factory settings, proceed
as follows:
1. Go to Settings > Data point configuration.
2. Press the Reset button.
ð The message Reset appears.
3. Press the Yes button to reset the data point configuration to the factory
settings.
4. Restart the device to activate the modified list of data points.
8.8.8.7 Exporting and importing the data point configuration
You can export the data point configuration, e.g., to back it up or import it
into another device. You will find more information in the Import/Export Man-
ager [►Section 8.28, Page 251] section.
8.9 Linking signals and events
The device enables you to link digital inputs (GPI) and control system com-
mands (SCADA) with device functions, digital outputs (GPO), and control
system messages.
The digital inputs available are each permanently linked to a Generic digital
input event message and the control system commands available are each
permanently linked to aGeneric SCADA command event message for this
purpose.
Input/command Event message
Digital input 1
1)
Generic digital input 1
Digital input 2
1)
Generic digital input 2
... ...
Digital input 42
1)
Generic digital input 42
Generic SCADA command 1 Generic SCADA command 1
Generic SCADA command 2 Generic SCADA command 2
... ...
Generic SCADA command 10 Generic SCADA command 10
Table38: Linking of digital inputs and control system commands with event messages
1)
The number of available digital inputs depends on the order-specific device
configuration.