14 Overview of parameters
Maschinenfabrik Reinhausen GmbH 2020 3013587317/21 EN TAPCON
®
14 Overview of parameters
This section contains an overview of the relevant menus and parameters.
The availability of individual parameters varies depending on your device
function.
Parameter Setting range Factory setting Current setting
Settings > Parameters > General
Language
2
See [Section 7.2, Page
78]
In accordance with order
IP address 0.0.0.0...255.255.255.255 192.0.1.230
Subnet mask 0.0.0.0...255.255.255.255 255.255.255.0
Gateway address 0.0.0.0...255.255.255.255 0.0.0.0
SSL encryption On; Off Off
Commissioning wizard Yes; No Yes
Measured value display Primary values; Secondary
values
Primary values
Transformer name - Transformer
Remote behavior HW, SCADA, HW+SCADA HW+SCADA
Settings > Parameters > Control
Desired value 1 49.0...140.0 V 100.0 V
Desired value 2 (optional)
Desired value 3 (optional)
Desired value 4 (optional)
Desired value 5 (optional)
Select the desired value (op-
tional)
Desired value 1..3 or de-
sired value 1...5
Desired value 1
Desired value specification maxi-
mum (optional)
49.0...140.0 V 120.0 V
Desired value specification mini-
mum (optional)
49.0...140.0 V 80.0 V
Desired value step width (op-
tional)
0.1 to 10.0 V 1.0 V
Activate TDSC (optional) On, Off Off
TDSC Umax (optional) 49.0...140.0 V 105.0 V
TDSC Umin (optional) 49.0...140.0 V 95.0 V
TDSC U0 (optional) 49.0...140.0 V 100.0 V
TDSC Pmax (optional) 0.1...1,000.0 MW 10.0 MW
TDSC Pmin (optional) -1,000.0...-0.1 MW -10.0 MW
Bandwidth 0.50...9.00% 1.00%
Delay time T1 1.0...600.0 s 40.0s