8 Operation
Maschinenfabrik Reinhausen GmbH 2020 1633587317/21 EN TAPCON
®
If you use this circuit, set the device as follows:
Parameter Option
Voltage-transformer circuit 3 Ph phase voltage
Current-transformer circuit 3 Ph phase current
Phase angle correction
Table47: Circuit 1-B
Circuit 1-C
L1
L2
L3
UL1
IL1
VT
CT1
UL1 IL1
IL2
IL3UL3
UL2
CT2
UL1-UL2
-UL2
IL1-IL2
-IL2
UI
L N k l
The voltage transformer VT is connected to the phase conductors L1 and
L2.
The current transformer CT1 is looped into the phase conductor L1 and
CT2 into the phase conductor L2.
The current transformers CT1 and CT2 are connected crosswise in paral-
lel (total current = I
L1
+I
L2
).
The total current I
L1
+I
L2
and voltage U
L1
-U
L2
are in phase.
The voltage drop on a phase conductor is determined by the current:
(I
L1
+I
L2
)/√3.
If you use this circuit, set the device as follows:
Parameter Option
Voltage-transformer circuit 3 Ph differential voltage
Current-transformer circuit 3 Ph total current
Phase angle correction
Table48: Circuit 1-C