8 Operation
Maschinenfabrik Reinhausen GmbH 2020208 3587317/21 ENTAPCON
®
Settings
Power fl...ing
Name Value
Reversal of power flow hysteresis 100kW
Reversal of power flow delay 5.0s
Behavior for reversal of power fl... Off
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin 31.01.2020 09:54
Figure143: Power flow monitoring
1. Go to Settings > Parameters > Grid > Power flow monitoring.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the Accept button to save the modified parameter.
Hysteresis
You can use this parameter to set the hysteresis. You can use this to avoid
the unnecessary generation of messages if the measured value fluctuates
around a threshold value.
Delay time
You can use this parameter to set the delay time in order to delay the issuing
of the event message.
Behavior for reversal of power flow
You can use this parameter to set the behavior in the event of a reversal of
power flow. You can select the following options:
Setting Behavior
Off The negative power flow is ignored.
Automatic regulation remains active.
Event only The Reversal of power flow event is issued.
If Z compensation is activated, this function is deacti-
vated.
Automatic regulation remains active.
Auto blocking The Reversal of power flow event is issued.
If Z compensation is activated, this function is deacti-
vated.
Automatic regulation is blocked.

Table of Contents