11 Event messages
Maschinenfabrik Reinhausen GmbH 2020 2873587317/21 EN TAPCON
®
No. Name Description Remedy
348 Generic digital input 38 There is a signal at the generic digital in-
put 38.
-
349 Generic digital input 39 There is a signal at the generic digital in-
put 39.
-
350 Generic digital input 40 There is a signal at the generic digital in-
put 40.
-
351 Generic digital input 41 There is a signal at the generic digital in-
put 41.
-
352 Generic digital input 42 There is a signal at the generic digital in-
put 42.
-
1229 Target tap position: Mas-
ter
The master has not reached the target
tap position.
Check the parameters, function, wiring
and motor-drive unit of the master. Acti-
vate MANUAL mode and then AUTO
mode.
1230 Target tap position: Fol-
lower
The follower has not reached the target
tap position.
Check the parameters, function, wiring
and motor-drive unit of the follower. Acti-
vate MANUAL mode and then AUTO
mode.
1231 Followers on the CAN
bus > 1
Several followers are present in the par-
allel operation group.
Check the current system configuration.
1232 Limit value Pos< follower Value has reached or fallen below the
limit value for tap position Pos< follower.
Check the current operating conditions of
the transformer of the follower and the
set parameter Pos< follower.
1233 Limit value Pos> follower Value has reached or exceeded the limit
value for tap position Pos> follower.
Check the current operating conditions of
the transformer of the follower and the
set parameter Pos> follower.
Table126: Event messages

Table of Contents