7 Commissioning
Maschinenfabrik Reinhausen GmbH 202086 3587317/21 ENTAPCON
®
5. Press on the follower to select auto mode.
ð The follower switches to the same tap position as the master.
6. Press on the master to select auto mode.
7. Press on the follower to select manual mode.
8. Press or on the follower to manually change the tap position.
ð After expiry of the set delay time for parallel operation errors [Page
191], there is a tap difference from the follower to the master.
9. Press several times on the follower to manually increase the tap po-
sition by the number of permitted steps ("Maximum permitted tap differ-
ence") and then one further step.
ð After expiry of the set delay time for parallel operation errors, there is a
tap difference to follower on the master.
ð After expiry of the set delay time for parallel operation errors, there is a
tap difference to master on the follower.
10. Press on the follower to select auto mode.
ð There is no response. All devices remain blocked.
11. Press on the master and follower to select manual mode.
12. Press or on the master and follower to manually set the de-
sired step.
ð The function tests for the tap synchronization method are complete.
Installation and commissioning of the device is complete.