XPS Unified Programmer’s Manual
7.2.1.124 MultipleAxesPTPulseOutputGet
Name
MultipleAxesPTPulseOutputGet Gets the configuration of pulse generation for PT
trajectory.
Input tests
- Refer to section 7.1: “Input Tests Common to all XPS Functions”.
- Checks group type (must be a MultipleAxes group): (-8)
- Checks group name: (-19)
Description
This function returns the last configuration of pulse generation of a PT trajectory, that
was previously set by MultipleAxesPTPulseOutputSet().
The pulse output configuration is defined with a start element, an end element, and a
time interval in seconds.
Example:
MultipleAxesPTPulseOutputSet(MyGroup, 3, 5, 0.01)
MultipleAxesPTPulseOutputGet(MyGroup) => 0,3,5,0.01 (0 is the error return,
meaning “ no error “)
One pulse will be generated every 10 ms between the start of the 3rd element and the
end of the 5th element.
Start element= 3
End element = 5
Time interval = 0.01 seconds.
Prototype
int MultipleAxesPTPulseOutputGet(
int SocketID,
char GroupName[250],
int * StartElement,
int * EndElement,
double * TimeInterval
)
Input parameters
SocketID int Socket identifier gets by the
“TCP_ConnectToServer” function.
GroupName char * Group name.
Output parameters
StartElement int * Start pulse element number.
EndElement int * End pulse element number.
TimeInterval double * Time interval between pulses (seconds).
189 EDH0373En1023 01/18