XPS Unified Programmer’s Manual
7.2.1.147 PositionerCompensatedFastPCOAbort
Name
PositionerCompensatedFastPCOAbort – Aborts the CIE fast compensated PCO puls
generation.
Input tests
- Refer to section 7.1: “Input Tests Common to all XPS Functions”.
- Checks the positioner name: (-18)
Description
This function aborts the CIE fast compensated PCO pulses generation. The pulses
generation is stopped immediately; no more pulses will be generated even if the
scanning positioner continues to move across the predefined firing positions. To stop
the scanning move, use GroupMoveAbort() function.
Prototype
int PositionerCompensatedFastPCOAbort(
int SocketID,
char * FullPositionerName
)
Input parameters
SocketID int Socket identifier gets by the
“TCP_ConnectToServer” function.
FullPositionerName char * Positioner name.
Output parameters
None.
Return (In addition to the results of “Input Tests Common to all XPS
Functions”)
• 0: No error.
• -8: Wrong object type for this command.
• -18: Positioner Name doesn't exist or unknown command.
225 EDH0373En1023 — 01/18