195
F3SG-R
User’s Manual
Chapter5 Wiring Examples(F3SG-RA Series)
Input/Output Circuit and Applications
E
5-2-12. Pre-Resest Mode using NPN Output
The following is the example of External Device Monitoring enabled, Pre-Reset mode, NPN output and
External Test in 0 V Active.
[DIP Switch settings] *2
: Indicates a switch position.
Configure functions with the DIP Switches before wiring.
[Wiring Example]
Function DIP-SW1 DIP-SW2
Receiver
EDM Enabled
Pre-Reset
NPN
Emitter External Test: 0 V Active
㻞㻻㻺
㻟㻻㻺 㻟㻻㻺
㻠㻻㻺 㻠㻻㻺
㻣㻻㻺
OSSD1 : Black
OSSD2 : White
24 VDC : Brown
Not used : Yellow
TEST : Black
Not used : White
24 VDC : Brown
0 VDC : Blue
Receiver
Emitter
0 VDC : Blue
AUX : Red
Not used : Pink
PRE-RESET : Gray
RESET : Yellow
S1: Test Switch (Connect the line to 24 V if this switch is not
required)
S2: Lockout/Interlock Reset Switch
S3: Pre-Reset Switch
KM1, KM2: External device feedback
M: 3-phase motor
PLC: Programmable controller
(Used for monitoring only. NOT related to safety system.)
S1
S2 S3
F39-JGA-L F39-JGA-D
Power Supply
+24 VDC
0 VDC
KM1
KM2
KM1
KM2
M
PLC *1
IN
Pre-Reset Switch(S3)
Beam state
Reset Switch (S2)
OSSD
Unblocked
Blocked
T1: Push time: must be T1 >= 300ms
T2: Pre-reset limit time between Pre-reset and Reset: must be T2 <= 60s
T3: Push time: must be T3 >= 300ms
T1
T2
T3
KM1 KM2
*1. When connecting to the PLC, the output mode must be
changed with the Configuration Tool.
*2. The functions are configurable with DIP Switch. Refer to
Chapter 3 Setting with DIP Switch for more information on
setting the functions by the DIP Switch.