11.2.6 PROG Mode does not Change to RUN
Condition: A syntax error or a self-diagnosed error that caused operation to stop has occurred.
Procedure 1
Check if the ERROR/ALARM LED is flashing.
Example:
If the ERROR/ALARM LED is flashing, check <11.2.1 If ERROR/ALARM LED is Flashing >.
Procedure 2
Execute a total check (FPWIN GR) or check/compile (FPWIN Pro) to determine the location of the
syntax error.
Using FPWIN GR
Select “Debug” on the menu bar, and select “Totally check program”. Click on the “Execute” button in the
total check dialog box.
Using FPWIN Pro
Select "Compile All" under "Project", or "Check" under "Object" on the menu bar.
As the dialog box is displayed, check the contents.