11-5
11.2.2 If ERROR LED is ON
Condition: The system watchdog timer has been activated and the operation of PLC has been
activated.
Procedure 1
Set the mode selector of PLC from RUN to PROG. mode and turn the power off and then on.
If the ERROR/ALARM LED is turned on again, there is probably an abnormality in the FP0R control
unit. Please contact your dealer.
If the ERROR/ALARm LED is flashed, go to chapter 11.2.1.
Procedure 2
Set the mode selector from PROG. to RUN mode.
If the ERROR/ALARM LED is turned on, the program execution time is too long. Check the program.
Check
(1) Check if instructions such as “JMP” or LOOPare programmed in such a way that a scan never finish.
(2) Check if interrupt instructions are executed in succession.
11.2.3 ALL LEDs are OFF
Procedure 1
Check wiring of power supply.
Procedure 2
Check if the power supplied to the FP-X control unit is in the range of the rating.
Be sure to check the fluctuation of the voltage.
Procedure 3
Disconnect the power supply wiring to the other devices if the power supplied to the FP-X control unit is
shared with them.
If the LED on the control unit turn on at this moment, increase the capacity of the power supply or
prepare another power supply for other devices.
Please contact your dealer for further questions.