15.4.2 Table of Self-Diagnostic Error
Error
code
Name
Opera-
tion
status
Description and steps to take
FP-e
FP0
FP0R
FP
FP-X
FP2
FP2SH
FP10SH
E20 CPU error Stops
Probably a hardware abnormality
⇒
Please contact your dealer.
A A A
E21
Stops
Probably an abnormality in the internal RAM.
⇒Please contact your dealer.
A A A
E22
E23
E24
E25
E25
memory
model
unmatch
Stops
The models of master memories are different.
Use the master memories created with the
same model.
A
*1)
E26
User’s
ROM error
Stops
FP-e,FP0,FP0R,FPΣ,and FP1
C14,C16:Probably a hardware abnormality.
⇒ Please contact your dealer.
A A A A A
A A A
FP-X:
When the master memory cassette is
mounted, the master memory cassette may
be damaged. Remove the master memory,
and check whether the ERROR turns off.
When the ERROR turned off, rewrite the
master memory as its contents are damaged,
and use it again.
When the ERROR does not turn off, please
contact your dealer.
FP1 C24,C40,C56,C72,and FP-M:
Probably an abnormality in the memory unit
⇒Program the memory unit again and try to
operate. If the same error is detected, try to
operate with another memory unit.
FP2,FP2SH,FP10SH,and FP3:
There may be a problem with the installed
ROM.
-ROM is not installed.
-ROM contents are damaged.
-Program size stored on the ROM is larger
than the capacity of the ROM
⇒
Check the contents of the ROM
E27
Unit
installation
error
Stops
Units installed exceed the limitations.(i.e.,4 or
more link units)
⇒ Turn off the power and re-configure units
referring to the hardware manual.
A A A A A A
E28
System
register
error
Stops
Probably an abnormality in the system
register.
⇒ Check the system register setting or
initialize the system registers.
A
*1) This error occurs on FP-X Ver2.0 or later. A: Available