Loading...
15-74
Error
code
Name
Opera-
tion
status
Description and steps to take
FP-e
FP0
FP0R
FP
Σ
FP-X
FP2
FP2SH
FP10SH
E41
Intelligent
unit error
Selec-
table
An abnormality in an intelligent unit.
FPΣ, FP-X:
Check the contents of special data register
DT90006and locate the abnormal FP
intelligent unit (application cassette for FP-X).
FP2,FP2SH,and FP10SH:
Check the contents of special data registers
DT90006,DT90007 and locate the abnormal
intelligent unit. Then check the unit referring
to its manual..
Selection of operation status using system
register22:
-to continue operation, set 1
-to stop operation, set 0
FP3:
Check the contents of special data registers
DT9006,DT9007 and locate the abnormal
intelligent unit. Then check the unit referring
to its manual..
Selection of operation status using system
register22:
-to continue operation, set 1
-to stop operation, set 0
Verification is possible in FPWIN GR/Pro at
“I/O errorin the status display function.
A A A A A
E42
I/O unit
verify error
Selec-
table
I/O unit(Expansion unit) wiring condition has
changed compared to that at time of power-
up.
Check the contents of special data register
(FP0: DT9010,
FPΣ, FP-X: DT90010,DT90011) and locate
the erroneous expansion unit.
It checks whether an expansion connector is
in agreement.
Check the contents of special data register
(FP2,FP2SH,and
FP10SH:DT90010,DT90011,FP3
DT9010,DT9011)
Selection of operation status using system
register23:
-to continue operation, set 1
-to stop operation, set 0
Verification is possible in FPWIN GR/Pro at
“I/O errorin the status display function.
A A A A A A A