11
2017 Page 241 5IN2413 B
Notes
Each option appears only if the relevant module (IP or GPRS module) is installed in the
system.
If your panel is equipped with an IP or GSM module you can start the download file
procedure by sending an SMS command to the panel in the following format:
(If address and port are configured and updated)
a. Via IP 97239637777IPFILE.
b. Via GSM (GPRS) 97239637777GSMFILE.
(Address and port can be added to the SMS command string as per the following. If
specified, these parameters also override any existing panel settings)
a. Via IP 97239637777IPFILE10.10.10.6:80.
b. Via GSM (GPRS) 97239637777GSMFILE212.150.25.223:80.
3.
Once selected, the ProSYS Plus will start downloading the required files. The
upgrade procedure may take approximately 40 minutes to complete. This will
vary according to whether the procedure is performed via GPRS or IP. Once the
files are downloaded the panel automatically starts with the upgrade procedure
of the units connected to the system
.
Notes
• During the upgrade process of the panel firmware there will be no display on the keypad.
• While downloading the files for the upgrade procedure the green STATUS LED on the
main panel PCB will flash slowly. When the upgrade procedure starts, it will start to flash
rapidly.
Step 4: Verify the upgrade was successful
1. From the main display press Exit ( ) and enter the installer code followed by
OK ( ).
2. Scroll to Maintenance Diagnostics Panel Version. The upgraded version
of the main panel will appear.
3. To view the other accessories version navigate to the required menus under the
Maintenance Diagnostics menu.
Note
If upgrade has failed, the previous software version of the main panel / accessory version
will appear.