Setting the ProSYS Plus to comply with EN 50131 Requirements
1. Access the Installer programming mode.
2. From the System menu select to access the Settings menu.
3. From the Settings menu select to access the Standard option.
4. Select EN 50131. Once selected, the following changes will occur in the ProSYS
Plus software:
Feature EN 50131 Compliance
Timers Quick Key Required Value:
Entry Delay
,
45 seconds (maximum
allowed)
AC Delay
Immediate (0 minutes)
Jamming Time
0 minutes
RX Supervision
2 hours
System Controls Quick Key
Required Value:
Quick Arm
Set to NO
False Code Trouble
Set to Yes
Forced Arming
Set to NO
Authorize installer
Set to YES
Override Trouble
Set to NO
Restore Alarm
Set to YES
Mandatory Event Log
Set to YES
Restore Trouble
Set to YES
Exit Alarm
Set to NO
Entry Alarm
Set to YES
20 minutes signal
Set to YES
Attenuation
Set to YES
• After Level 2, 3 or 4 users (users with access codes) are no longer accessing
the system, indications are made inaccessible to Level 1 users (users who
don’t have a code) by the display showing only "Enter code:"
• After entering 3 invalid user codes, an 'invalid code' signal will be alerted
to the monitoring station and recorded in the event log. The invalid code
will continue to alert in the system until restored by a user with a code