120 Configuring an Alarm
Figure70:Alarms Form
1.Name Box 2.Level Box 3.Latch Box 4.Trap Box 5.Log Box 6.LED & Relay Box 7.Refresh Time Box 8.Apply Button
9.Reload Button
3. Configure the following parameter(s) as required:
Parameter Description
Name Synopsis:  Any 34 characters
Default:  sys_alarm
The alarm name, as obtained through the alarms CLI command.
Level Synopsis:  { EMRG, ALRT, CRIT, ERRO, WARN, NOTE, INFO, DEBG }
Severity level of the alarm:
• EMERG - The device has had a serious failure that caused a
system reboot.
• ALERT - The device has had a serious failure that did not cause a
system reboot.
• CRITICAL - The device has a serious unrecoverable problem.
• ERROR - The device has a recoverable problem that does not
seriously affect operation.
• WARNING - Possibly serious problem affecting overall system
operation.
• NOTIFY - Condition detected that is not expected or not
allowed.
• INFO - Event which is a part of normal operation, e.g. cold start,
user login etc.
• DEBUG - Intended for factory troubleshooting only.
This parameter is not configurable.
Latch Synopsis:  { On, Off }
Default:  Off
Enables latching occurrence of this alarm in the Alarms Table.
Trap Synopsis:  { On, Off }
Default:  Off
Enables sending an SNMP trap for this alarm.
Log Synopsis:  { On, Off }
Default:  Off