Input Module Reference Data
1-Port and 3-Port E1 Input Modules
148 SSU-2000 User’s Guide 12713020-002-2 Revision D – April 2004
Alarms Caused by Hardware Problems
The following alarms are generated due to hardware problems:
External Clock Signal PLL Unlocked
– Report event message and perform any other actions as required by the
user-set severity level
– Fault channel, even if severity is less than MAJOR
– Monitor PLL for recovery
Input Signal PLL Unlocked
– Report event message and perform other actions as required by severity
– Fault port, regardless of severity.
– Monitor PLL for recovery
Phase Measurement Circuitry Fault
– Report event message and perform any other required actions
– Fault Port
– Monitor phase hardware for recovery
Alarms Caused by Faulty Input Signals
The following alarms are caused by problems with the incoming input signal’s
formatting or content:
Errors Tracked:
– Framed signals: LOS, AIS, OOF, BPV and CRC
– Unframed signals: LOS
Error and Clear Counters
The E1 Input module maintains a count of the number of consecutive errored
seconds for each error type for each port. Once this error count exceeds a user-set
limit, the input signal which has experienced the errors said to be in episode. Refer
to Changing Factory Defaults, on page 100, for more information on setting the error
count.
The Input module maintains a count of the number of consecutive seconds in which
the input signal for each port is free of each type of error. This clear count must
exceed a user-set limit before the input signal is no longer in episode. Refer to
Changing Factory Defaults, on page 100, for more information on setting the clear
count.
Handling Input Signal Faults
For LOS (loss of signal) and before going into episode:
Coast over brief occurrences of LOS, reporting the last known good phase
measurements for the port until signal returns or the signal goes into episode
The duration of a brief occurrence of LOS is defined by the value of the error
count for LOS. The default is 10 seconds.