12713020-002-2 Revision D – April 2004 SSU-2000 User’s Guide 97
Provisioning and Operating the SSU-2000
Initial Provisioning
Provisioning Output Modules
This section describes how to enable and provision Output modules. such as DS1,
E1, or Composite Clock. You must enable and provision each output port as
appropriate. You can install Output modules in any slot in the main SSU-2000 shelf
and in the SDU-2000 Expansion Shelf.
1. Enable the modules.
ICS command:
Type
OUTPUT xAy ENABLE, then press Enter, where x is the slot number and y is
the port number. Repeat this command for each port and each slot.
TL1 command:
SET-PRMTR-OUTPUT::SxA[y[-z]]:123::ON;
where x is the shelf number, y is the slot number, and z is the port number.
Repeat this command for each shelf, port, and slot.
2. Provision the output module as appropriate.
ICS command:
Refer to the OUTPUT command description in Interactive Command Set, on
page 315, for details on all command options.
TL1 command:
Refer to the SET-PRMTR-OUT commands for the various Output modules in TL1
Command Interface, on page 266.
3. DIsable unused output ports to prevent spurious alarms.
ICS command:
Type
OUTPUT xAy DISABLE, then press Enter, where x is the slot number and y
is the port number. Repeat this command for each unused port and slot.
TL1 command:
SET-PRMTR-OUTPUT::SxAy[-z]:123::OFF;
where x is the shelf number, y is the slot number, and z is the port number.
Repeat this command for each shelf, port, and slot.
4. If a DS1 input signal is not available, bypass the Clock C source for all output
modules.
ICS command:
Type
OUTPUT BYPASS OFF, then press Enter.
TL1 command:
SET-PRMTR-OUTPUT::SxAy[-z]:123::,,,OFF;
where x is the shelf number, y is the slot number, and z is the port number.
Repeat this command for each shelf and Output module.