12713020-002-2 Revision D – April 2004 SSU-2000 User’s Guide 93
Provisioning and Operating the SSU-2000
Initial Provisioning
1. Connect a computer to the SSU-2000 using the procedure in Establishing a
Connection With the SSU-2000, on page 88. The
SSU-2000> prompt appears.
2. Log in to the SSU-2000:
ICS command:
Type
login followed by the administrator’s user name and press Enter. The
system prompts for a password. Type the administrator’s password and press
Enter. The system prompt
SSU-2000> appears.
TL1 command:
Type
ACT-USER::uid:123::pwd;
where uid and pwd are the administrator’s user id and password, respectively;
123 is an arbitrary ctag value.
3. Provision the reference selection mode. Priority is the default reference selection
mode, and the most widely used mode. See Selecting the Input, on page 30, for
information on selecting the appropriate mode.
ICS command:
Type
REF MODE PRI then press Enter.
TL1 command:
Type
SET-INPUT-REF:::123::port,PRI;
where 123 is an arbitrary ctag value and port is the selected input port in the
format S1Ax[-z], where x is the slot number (3–12) and z is the channel number
(1–3).
Repeat this command for all inputs.
4. Provision the clocks to enable auto-return (revertive) mode. Symmetricom
generally recommends that auto-return be set to On, unless both clocks are of
the same Stratum level. See Setting the Reference Switching Mode, on page 31,
for more information on revertive and non-revertive modes.
ICS command:
Type
CLK AR ON then press Enter.
TL1 command:
SET-CLK-AR:::123::ON;
5. Provision the IP, Gateway, and Subnet addresses for the SSU-2000. The IT
department or site administrator for your location can recommend specific
addresses for these parameters. Use the format xxx.xxx.xxx.xxx for the address.
ICS commands:
Type
IP ADDR [ip address] then press Enter.
Type
IP GATEWAY [gate address] then press Enter.
Type
IP SUBNET [subnet address] then press Enter.

Table of Contents

Other manuals for Symmetricom SSU-2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom SSU-2000 and is the answer not in the manual?

Symmetricom SSU-2000 Specifications

General IconGeneral
BrandSymmetricom
ModelSSU-2000
CategoryPower Supply
LanguageEnglish

Related product manuals