Advanced Operation
7.4.3 Setting Motor Constants
7-40
J
Motor Iron-Core Loss with Torque Compensation: E2-10 (for SPEC: F)
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
E2-10
Motor iron-core loss
with torque com-
pensation
×
0 to 65535
W
14
A A
× ×
D
The default setting depends upon the Inverter capacity. The above table shows the settings for 200V
class, 0.4 kW Inverter. (See page 8 - 47)
D
The motor iron-core loss is set in “W” units.
D
Normally, the settings do not need to be altered. However, if the Inverter and motor capacities are vast-
ly different, set the E2-10 value for the same Inverter capacity as the applicable motor. (See page
8 - 47)
7

Table of Contents