EasyManua.ls Logo

YASKAWA CIMR-G5A Series - Page 234

YASKAWA CIMR-G5A Series
355 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.5.5 External Terminal Functions: H
7-80
D
The analog input signal level, gain, and bias are set with the following constants.
Terminal 16 signal level selector
H3-04 (0 to +10 V or 0 to
±
10 V)
Terminal 16 input gain H3-06
Terminal 16 input bias H3-07
Terminal 14 signal level selector H3-08 (0 to +10 V, 0 to ±10 V, or 4 to 20 mA)
Terminal 14 input gain H3-10
Terminal 14 input bias H3-11
D
When a voltage input is being input to terminal 14, be sure to disconnect jumper wire J1 on the control
PC board.
D The input resistance will be destroyed if a voltage input is used without disconnecting the jumper wire.
(Refer to Torque Reference Settings: H3-04, H3-05, H3-08, H3-09 in 7.3.3.)
D
Set the time constant in constant H3-12 when adding a primary delay filter to an analog input. This
filter time constant applies to all three of the analog inputs.
D
Settings 2 and D cannot be set at the same time. OPE07 will be detected.