Wiring
3.7.3 Wiring a PG Speed Control Card
3-30
J PG-D2 (For V/f with PG Feedback Mode Only)
PG
Power supply +12 V
Power supply 0 V
Pulse monitor output
Pulse input − (A/B phase)
Power supply +5 V
Pulse input + (A/B phase)
Three-phase 200 VAC
(400 VAC)
VS-616G5
4CN
12
R
S
T
U
V
W
IM
PG-D2
4CN
TA1
E
TA2 (E)
1
2
3
4
5
6
7
8
D Shielded twisted-pair wires must be used for signal lines.
D Do not use the pulse generator’s power supply for anything other than the pulse
generator (encoder). Using it for another purpose can cause malfunctions due
to noise.
D The length of the pulse generator’s wiring must not be more than 100 meters.
Fig 3.28 PG-D2 Wiring
J PG-X2 (For Flux Vector Control Mode Only)
IM
PG-X2
4CN
Power supply +12 V
Power supply 0 V
B-phase pulse monitor output
TA2
E
TA3 (E)
1
TA1
A-phase pulse monitor output
A-phase pulse input (−)
A-phase pulse input (+)
B-phase pulse input (−)
Z-phase pulse monitor output
9
10
B-phase pulse input (+)
Power supply +5 V
Three-phase 200 VAC
(400 VAC)
4CN
12
R
S
T
U
V
W
VS-616G5
2
3
4
5
6
7
8
1
2
3
4
5
6
7
D Shielded, twisted-pair wire must be used for signal lines.
D Do not use the pulse generator’s power supply for anything other than the
pulse generator (encoder). Using it for another purpose can cause
malfunctions due to noise.
D The length of the pulse generator’s wiring must not be more than 100 meters.
D The direction of rotation of the PC can be set in user constant F1-05. The
factory preset if for forward rotation, A-phase advancement.
PG
Fig 3.29 PG-X2 Wiring