Setting User Constants
4.2.5 Initialize Mode
4-24
Programming
Only the user constants specified in A2-01 through A2-32 can be displayed or
set.
Autotuning
The user constants cannot be displayed.
Modified constants
The user constants cannot be displayed.
A
EXAMPLE
"
Setting C1-08 (Deceleration Time 4) in A2-01 to Define it as a User Constant
Step Key Sequence Digital Operator Display Remarks
1
MENU
G5: Main Menu :
Operation
2
G5: Main Menu :
Initialize
3
DATA
ENTER
Select Language
English
4
Function A2
User Constants
5
DATA
ENTER
User Param 1
A2−01 = −−−−−
6
DATA
ENTER
User Param 1
−−−−−−−
The first digit blinks.
7
Press twice.
User Param 1
C1−01
8
Press twice.
RESET
User Param 1
C1−01
Writes-in set value 0000.
9
Press 7 times.
User Param 1
C1−08
10
DATA
ENTER
Entry Accepted
Writes-in the new setting.
User Param 1
A2−01 = C1−08
After a few seconds, the Operator dis-
play is as shown on the left.
11
ESC
Function A2
User Constants
12
Press twice.
Access Level
Advanced
13
DATA
ENTER
A1−01 = 4:::
Advanced
14
Press twice.
A1−01 = 1
User Program
The user program access level can be
set only after one or more constants
are set as user constants in A2-01 to
A2-32. If no constants are set, the
user program access level will not be
displayed for A1-01.
15
DATA
ENTER
Entry Accepted
Writes-in the new setting.
A1−01 = 4:::
Advanced
If the DATA/ENTER Key is not
pressed within one minute, the Oper-
ator display will return as shown on
the left. In this case, repeat from step
14.
4