5.1 A: Initialization
130 YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Saving User Parameters
To save specific parameters to A2-01 to A2-32, first set the access level to allow access to all parameters (A1-02 = 2).
Next assign the parameter number to the User Parameters list by entering it into one of the A2- parameters. If A1-01
is then set to 1, the access level can be restricted so that users can only set and refer to the specific parameters saved as
User Parameters.
A2-33: User Parameter Automatic Selection
A2-33 determines whether or not parameters that have been edited are saved to the User Parameters (A2-17 to A2-32) for
quick, easy access.
Setting 0: Do not save list of recently viewed parameters.
To manually select the parameters listed in the User Parameter group, set A2-33 to 0.
Setting 1: Save history of recently viewed parameters.
By setting A2-33 to 1, all parameters that were recently edited will be automatically saved to A2-17 through A2-32. A
total of 16 parameters are saved with the most recently edited parameter set to A2-17, the second most recently to A2-18,
and so on. User Parameters can be accessed using the Setup Mode of the digital operator.
No. Parameter Name Setting Range Default
A2-33 User Parameter Automatic Selection 0 or 1 Determined by A1-06
SIEP_C710616_35.book 130 ペー 2015年11月30日 月曜日 午後2時2分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA E1000 and is the answer not in the manual?

YASKAWA E1000 Specifications

General IconGeneral
BrandYASKAWA
ModelE1000
CategoryController
LanguageEnglish

Related product manuals