5.6 F: Option Settings
180 YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Setting 1: Multi-step speed operation enabled
Even if the NetRef command is selected, multi-step speed inputs are still active and can override the frequency reference
from the communications option (like Yaskawa V7 drives).
F6-08: Reset Communication Parameters
Determines whether communication-related parameters (F6-) are reset when the drive is initialized using parameter
A1-03.
Setting 0: Do not reset parameters F6- when the drive is initialized with A1-03
Setting 1: Reset F6- when the drive is initialized with A1-03
Note: F6-08 is not reset when the drive is initialized, but does determine whether initializing the drive with A1-03 resets the other
communication parameters, F6-.
CC-Link Parameters
Parameters F6-04, F6-10, F6-11, and F6-14 set up the drive to operate on a CC-Link network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option CC-Link Installation Manual
and Technical Manual.
MECHATROLINK Parameters
Parameters F6-20 through F6-26 set up the drive to operate on a MECHATROLINK network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option MECHATROLINK-II
Installation Manual and Technical Manual.
PROFIBUS-DP Parameters
Parameters F6-30 through F6-32 set up the drive to operate on a PROFIBUS-DP network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option PROFIBUS-DP Installation
Manual and Technical Manual.
CANopen Parameters
Parameters F6-35 and F6-36 set up the drive to operate on a CANopen network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option CANopen Installation Manual
and Technical Manual.
DeviceNet Parameters
Parameters F6-50 through F6-63 set up the drive to operate on a DeviceNet network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option DeviceNet Installation Manual
and Technical Manual.
No. Parameter Name Setting Range Default
F6-08 Reset Communication Parameters 0, 1 0