EasyManuals Logo

YASKAWA E1000 User Manual

YASKAWA E1000
480 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #180 background imageLoading...
Page #180 background image
5.6 F: Option Settings
180 YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Setting 1: Multi-step speed operation enabled
Even if the NetRef command is selected, multi-step speed inputs are still active and can override the frequency reference
from the communications option (like Yaskawa V7 drives).
F6-08: Reset Communication Parameters
Determines whether communication-related parameters (F6-) are reset when the drive is initialized using parameter
A1-03.
Setting 0: Do not reset parameters F6- when the drive is initialized with A1-03
Setting 1: Reset F6- when the drive is initialized with A1-03
Note: F6-08 is not reset when the drive is initialized, but does determine whether initializing the drive with A1-03 resets the other
communication parameters, F6-.
CC-Link Parameters
Parameters F6-04, F6-10, F6-11, and F6-14 set up the drive to operate on a CC-Link network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option CC-Link Installation Manual
and Technical Manual.
MECHATROLINK Parameters
Parameters F6-20 through F6-26 set up the drive to operate on a MECHATROLINK network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option MECHATROLINK-II
Installation Manual and Technical Manual.
PROFIBUS-DP Parameters
Parameters F6-30 through F6-32 set up the drive to operate on a PROFIBUS-DP network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option PROFIBUS-DP Installation
Manual and Technical Manual.
CANopen Parameters
Parameters F6-35 and F6-36 set up the drive to operate on a CANopen network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option CANopen Installation Manual
and Technical Manual.
DeviceNet Parameters
Parameters F6-50 through F6-63 set up the drive to operate on a DeviceNet network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option DeviceNet Installation Manual
and Technical Manual.
No. Parameter Name Setting Range Default
F6-08 Reset Communication Parameters 0, 1 0
SIEP_C710616_35.book 180 ペー 2015年11月30日 月曜日 午後2時2分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA E1000 and is the answer not in the manual?

YASKAWA E1000 Specifications

General IconGeneral
BrandYASKAWA
ModelE1000
CategoryController
LanguageEnglish

Related product manuals