B.4 Control Mode Dependent Parameter Default Values
398 YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
B.4 Control Mode Dependent Parameter Default Values
The tables below list parameters that depend on the control mode selection. These parameters are initialized to the shown
values if the control mode is changed.
◆ A1-02 Dependent Parameters
Table B.2 A1-02 Dependent Parameters and Default Values
No. Name Setting Range Resolution
Control Modes (A1-02)
V/f (0) OLV/PM (5)
b2-01 DC Injection Braking Start Frequency 0.0 to 10.0 0.1 0.5 Hz 0.5 Hz
b2-04
<9> Default setting is determined by the drive model (o2-04).
<14> Default setting value is dependent on the motor code set to parameter E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<52> This setting value depends on a Maximum Applicable Motor Capacity and V/f pattern selection in parameter E1-03.
<53> This setting value depends on a Maximum Applicable Motor Capacity: 1000 s in models CIMR-E2A0110 to 2A0415 and CIMR-
E4A0103 to 4A1200.
DC Injection Braking Time at Stop 0.00 to 10.00 0.01 s 0.50 0.00
b3-01 Speed Search Selection at Start 0 to 1 – 0 0
b3-02 Speed Search Deactivation Current 0 to 200 1% 120 –
b5-15 PID Sleep Function Start Level 0.0 to 200.0 0.1 0.0 Hz 0.0 Hz
b8-01 Energy Saving Control Selection 0 to 1 – 0 –
C1-11 Accel/Decel Time Switching Frequency 0.0 to 200.0 0.1 0.0 Hz 0.0 Hz
C2-01 S-Curve Time at Acceleration Start 0.00 to 10.00 0.01 s 0.20 1.00
C4-01 Torque Compensation Gain 0.00 to 2.50 0.01 1.00 0.00
C4-02 Torque Compensation Primary Delay Time 0 to 10000 1 ms 200 <53> 100
C6-02 Carrier Frequency Selection 1 to F – 0.0 Hz 0.0 Hz
d3-01 Jump Frequency 1 0.0 to 200.0 0.1 0.0 Hz 0.0 Hz
d3-02 Jump Frequency 2 0.0 to 200.0 0.1 0.0 Hz 0.0 Hz
d3-03 Jump Frequency 3 0.0 to 200.0 0.1 0.0 Hz 0.0 Hz
d3-04 Jump Frequency Width 0.0 to 20.0 0.1 1.0 Hz 1.0 Hz
E1-04 Maximum Output Frequency 40.0 to 200.0 0.1 Hz 60.0 <14>
E1-05 Maximum Voltage <18> 0.0 to 255.0 0.1 V 200.0 <52> <14>
E1-06 Base Frequency 0.0 to 200.0 0.1 Hz 50.0 <52> <14>
E1-07 Middle Output Frequency 0.0 to 200.0 0.1 Hz 3.0 <52> –
E1-08 Middle Output Frequency Voltage <18> 0.0 to 255.0 0.1 V 15.0 <52> –
E1-09 Minimum Output Frequency 0.0 to 200.0 0.1 Hz 1.5 <52> <14>
E1-10 Minimum Output Frequency Voltage <18> 0.0 to 255.0 0.1 V 9.0 –
L1-01 Motor Overload Protection Selection 0 to 4 – 1 4
L3-20 DC Bus Voltage Adjustment Gain 0.00 to 5.00 0.01 1.00 0.65
L3-21 Accel/Decel Rate Calculation Gain 0.00 to 200.00 0.01 1.00 2.50
L4-01 Speed Agreement Detection Level 0.0 to 200.0 0.1 0.0 Hz 0.0 Hz
L4-02 Speed Agreement Detection Width 0.0 to 20.0 0.1 2.0 Hz 2.0Hz
L4-03 Speed Agreement Detection Level (+/-) -200.0 to 200.0 0.1 0.0 Hz 0.0 Hz
L4-04 Speed Agreement Detection Width (+/–) 0.0 to 20.0 0.1 2.0 Hz 2.0Hz
L8-38 Carrier Frequency Reduction Selection 0 to 2 1 <9> 0
L8-40 Carrier Frequency Reduction Off Delay Time 0.00 to 2.00 0.01 s 0.50 0.00
o1-03 Digital Operator Display Selection 0 to 3 1 0 0