EasyManuals Logo

YASKAWA E1000 User Manual

YASKAWA E1000
480 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #446 background imageLoading...
Page #446 background image
D.3 UL Standards
446 YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
D.3 UL Standards
UL Standards Compliance
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product
testing and evaluation, and determined that their stringent standards for product safety have been met. For a product to
receive UL certification, all components inside that product must also receive UL certification.
Figure D.6
Figure D.6 UL/cUL Mark
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions
described below must be met to maintain compliance when using this drive in combination with other equipment:
Note: Model CIMR-E4A0930 and 4A1200 is UL compliant when the air entering the drive-installed panel or cabinet is 45°C or less.
For more information, contact your nearest Yaskawa representative or our sales office.
Installation Area
Do not install the drive to an area greater than pollution degree 2 (UL standard).
Ambient Temperature
IP20/NEMA 1, UL Type 1 enclosure: -10°C to +40°C
IP00 enclosure: -10°C to +50°C
Main Circuit Terminal Wiring
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL/cUL approval requires the use of UL
Listed closed-loop crimp terminals when wiring the drive main circuit terminals on models CIMR-E2A0110 to
2A0415 and 4A0058 to 4A1200. Use only the tools recommended by the terminal manufacturer for crimping.
The wire gauges listed in Table D.4 and Table D.5 are Yaskawa recommendations. Refer to local codes for proper wire
gauge selections.
Table D.4 Wire Gauge and Torque Specifications (Three-phase 200 V Class)
Model
CIMR-E
Terminal
For Europe and China <1> For U.S.A. <2> For Asia <3>
Screw
Size
Tightening
Torque
Nm (lb.in.)
Recommended
Gauge
mm
2
Applicable
Gauge
mm
2
Recommended
Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Recommended
Gauge
mm
2
Applicable
Gauge
mm
2
2A0004
2A0006
2A0008
2A0010
R/L1, S/L2, T/L3 2.5 2.5 to 6 14 14 to 10 2 2 to 5.5
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 2.5 2.5 to 6 14 14 to 10 2 2 to 5.5
–, +1, +2 2.5 to 6 14 to 10 2 2 to 5.5
2.5 2.5 to 6 10 14 to 10 2 2 to 5.5
2A0012
R/L1, S/L2, T/L3 2.5 2.5 to 6 12 14 to 10 2 2 to 5.5
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 2.5 2.5 to 6 14 14 to 10 2 2 to 5.5
–, +1, +2 2.5 to 6 14 to 10 2 2 to 5.5
2.5 2.5 to 6 10 14 to 10 3.5 2 to 5.5
2A0021
R/L1, S/L2, T/L3 4 2.5 to 6 10 12 to 10 5.5 3.5 to 5.5
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 2.5 2.5 to 6 10 12 to 10 3.5 3.5 to 5.5
–, +1, +2 4 to 6 12 to 10 5.5 3.5 to 5.5
4 4 to 6 10 12 to 10 3.5 3.5 to 5.5
2A0030
R/L1, S/L2, T/L3 6 4 to 16 8 10 to 6 14 5.5 to 14
M4
2.1 to 2.3
(18.4 to 20.4)
U/T1, V/T2, W/T3 6 4 to 16 8 10 to 6 8 5.5 to 14
–, +1, +2 6 to 16 10 to 6 14 5.5 to 14
6 6 to 10 8 10 to 8 5.5 5.5 to 8 M5
2 to 2.5
(17.7 to 22.1)
SIEP_C710616_35.book 446 ペー 2015年11月30日 月曜日 午後2時2分