EasyManuals Logo

YASKAWA E1000 User Manual

YASKAWA E1000
480 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #413 background imageLoading...
Page #413 background image
C.2 Communication Specifications
MEMOBUS/Modbus
Communications
C
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual 413
C.2 Communication Specifications
MEMOBUS/Modbus specifications appear in the following table:
Item Specifications
Interface RS-422, RS-485
Communications Cycle Asynchronous (Start-stop synchronization)
Communication Parameters
Communication Speeds Available 1.2; 2.4; 4.8; 9.6; 19.2; 38.4; 57.6; 76.8; 115.2 kbps
Data length 8 bit (fixed)
Parity Select even, odd, or none
Stop bit 1 bit (fixed)
Protocol MEMOBUS/Modbus (using RTU mode only)
Max Number of Slaves 31 drives