B.3 Parameter Table
382 YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
L: Protection Function
L parameters provide protection to the drive and motor, such as: control during momentary power loss, Stall Prevention,
frequency detection, fault restarts, overtorque detection, and other types of hardware protection.
L1: Motor Protection
L2: Momentary Power Loss Ride-Thru
No. (Addr.) Name Description Setting Page
L1-01
(480H)
<10> Default setting is determined by the control mode (A1-02).
Motor Overload Protection
Selection
0: Disabled
1: Standard Fan Cooled
4: PM motor with variable torque
The drive may not be able to provide protection when multiple motors are used, even if
overload is enabled in L1-01. Set L1-01 to 0 and install separate thermal relay to each motor.
Default: <10>
Min: 0
Max: 4
209
L1-02
(481H)
Motor Overload Protection Time
Sets the motor thermal overload protection (oL1) time.
Default: 1.0 min
Min: 0.1 min
Max: 5.0 min
210
L1-03
(482H)
Motor Overheat Alarm Operation
Selection (PTC input)
Sets operation when the motor temperature analog input (H3-02, H3-06, or H3-10 = E) exceeds
the oH3 alarm level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in C1-09)
3: Alarm only (“oH3” will flash)
Default: 3
Min: 0
Max: 3
211
L1-04
(483H)
Motor Overheat Fault Operation
Selection (PTC input)
Sets stopping method when the motor temperature analog input (H3-02, H3-06, or H3-10 = E)
exceeds the oH4 fault level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in C1-09)
Default: 1
Min: 0
Max: 2
212
L1-05
(484H)
Motor Temperature Input Filter
Time (PTC input)
Adjusts the filter for the motor temperature analog input (H3-02, H3-06, or H3-10 = E).
Default: 0.20 s
Min: 0.00 s
Max: 10.00 s
212
L1-13
(46DH)
Continuous Electrothermal
Operation Selection
0: Disabled
1: Enabled
Default: 1
Min: 0
Max: 1
212
L1-15
(440H)
Motor 1 Thermistor Selection
(NTC)
0: Disabled
1: Enabled
Note: This parameter is available in models CIMR-E4A0930 and 4A1200.
Default: 0
Min: 0
Max: 1
213
L1-16
(441H)
Motor 1 Overheat Temperature
Sets the temperature for motor 1 that triggers an overheat fault (oH5).
Note: This parameter is available in models CIMR-E4A0930 and 4A1200.
Default: 120
Min: 50
Max: 200
213
L1-19
(444H)
Operation at Thermistor
Disconnect(THo) (NTC)
Determines what action the drive should take when a thermistor disconnect fault occurs (Tho).
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in C1-09)
3: Alarm only ("THo" will flash)
Note: This parameter is available in models CIMR-E4A0930 and 4A1200.
Default: 3
Min: 0
Max: 3
214
L1-20
(445H)
Operation at Motor Overheat
(oH5)
Det
ermines what action th
e drive should take when a motor overheat fault occurs (oH5).
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in C1-09)
3: Alarm only ("oH5" will flash)
Note: This parameter is available in models CIMR-E4A0930 and 4A1200.
Default: 1
Min: 0
Max: 3
214
No. (Addr.) Name Description Setting Page
L2-01
(485H)
Momentary Power Loss Operation
Selection
0: Disabled. Drive trips on (Uv1) fault when power is lost.
1: Recover within L2-02. Uv1 will be detected if power loss is longer than L2-02.
2: Recover as long as CPU has power. Uv1 is not detected.
3: KEB Ride-Thru operation within L2-02.
4: KEB Ride-Thru as long as CPU has power.
5: Ramp to Stop with KEB deceleration.
Default: 0
Min: 0
Max: 5
214
L2-02
(486H)
Momentary Power Loss Ride-Thru
Time
Sets the Power Loss Ride-Thru time. Enabled only when L2-01 = 1 or 3.
Default:
<9>
Min: 0.0 s
Max: 25.5 s
219
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
SIEP_C710616_35.book 382 ペー 2015年11月30日 月曜日 午後2時2分