EasyManuals Logo

YASKAWA E1000 User Manual

YASKAWA E1000
480 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #292 background imageLoading...
Page #292 background image
6.10 Troubleshooting without Fault Display
292 YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
Drive Frequency Reference Differs from the Controller Frequency Reference
Command
Excessive Motor Oscillation and Erratic Rotation
Deceleration Takes Longer Than Expected with Dynamic Braking Enabled
Noise From Drive or Motor Cables When the Drive is Powered On
Earth Leakage Circuit Breaker (ELCB) Trips During Run
Incorrect frequency reference setting.
Check the multi-function analog input settings. Multi-function analog input terminal A1, A2, or A3 is set for
frequency gain (H3-02, H3-10, or H3-06 is set to “1”), but there is no voltage or current input provided.
Make sure H3-02, H3-10, and H3-06 are set to the proper values.
See if the analog input value is set to the right value (U1-13 to U1-15).
The Stall Prevention level during acceleration and deceleration set
too low.
Check the Stall Prevention level during acceleration (L3-02).
If L3-02 is set too low, acceleration may be taking too long.
Increase L3-02.
The Stall Prevention level during run has been set too low.
Check the Stall Prevention level during run (L3-06).
If L3-06 is set too low, speed will drop as the drive outputs torque.
Increase the setting value.
Drive reached the limitations of the V/f motor control method.
The motor cable may be long enough (over 50 m) to require Auto-Tuning for line-to-line resistance.
Be aware that V/f Control is comparatively limited when it comes to producing torque at low speeds.
Consider switching to Open Loop Vector Control.
Cause Possible Solutions
The analog input gain and bias for the frequency reference input
are set to incorrect values.
Check the gain and bias settings for the analog inputs that are used to set the frequency reference. Check parameters
H3-03 and H3-04 for input A1, check parameters H3-11 and H3-12 for input A2, and check parameters H3-07 and
H3-08 for input A3.
Set these parameters to the appropriate values.
A frequency bias signal is being entered via analog input terminals
A1 to A3.
If more than one of multi-function analog inputs A1 to A3 is set for frequency reference bias (H3-02, H3-10, or H3-06
is set to “0”), then the sum of all signals builds the frequency reference.
Make sure that H3-02, H3-10, and H3-06 are set appropriately.
Check the input level set for terminals A1 to A3 (U1-13 to U1-15).
PI control is enabled, and the drive is consequently adjusting the
output frequency to match the PI setpoint. The drive will only
accelerate to the maximum output frequency set in E1-04 while PI
control is active.
If PI control is not necessary for the application, disable it by setting b5-01 to “0”.
Cause Possible Solutions
Poor balance between motor phases. Check drive input power voltage to ensure that it provides stable power.
Hunting prevention function is disabled. Enable Hunting Prevention (n1-01 = 1).
Cause Possible Solutions
L3-04 is set incorrectly.
Check the Stall Prevention level during deceleration (L3-04).
If a dynamic braking option has been installed, disable Stall Prevention during deceleration (L3-04 = 0).
The deceleration time is set too long. Set deceleration to more appropriate time (C1-02).
Insufficient motor torque.
Assuming parameter settings are normal and that no overvoltage occurs when there is insufficient torque, it is likely
that the demand on the motor has exceeded the motor capacity.
Use a larger motor.
Reaching the torque limit.
If multi-function analog input terminal A1, A2, or A3 is set to torque limit (H3-02, H3-10, or H3-06 equals 10, 11, 12,
or 15), ensure that the analog input levels are set to the correct levels.
Ensure H3-02, H3-10, and H3-06 are set to the right levels.
Ensure the analog input is set to the correct value (U1-13 to U1-15).
Load exceeded the internal torque limit determined by the drive
rated current.
Switch to a larger capacity drive.
Cause Possible Solutions
Relay switching in the drive generates excessive noise.
Lower the carrier frequency (C6-02).
Install a noise filter on the input side of drive input power.
Install a noise filter on the output side of the drive.
Place the wiring inside a metal conduit to shield it from switching noise.
Ground the drive and motor properly.
Separate the main circuit wiring and the control lines.
Make sure wires and the motor have been properly grounded.
Cause Possible Solutions
Excessive leakage current trips ELCB.
Increase the ELCB sensitivity or use ELCB with a higher threshold.
Lower the carrier frequency (C6-02).
Reduce the length of the cable used between the drive and the motor.
Install a noise filter or reactor on the output side of the drive. Set the carrier frequency to 2 kHz when connecting a
reactor.
Cause Possible Solutions
SIEP_C710616_35.book 292 ペー 2015年11月30日 月曜日 午後2時2分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA E1000 and is the answer not in the manual?

YASKAWA E1000 Specifications

General IconGeneral
BrandYASKAWA
ModelE1000
CategoryController
LanguageEnglish

Related product manuals