5.9 n: Special Adjustments
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual 245
■ n8-65: Speed Feedback Detection Control Gain during ov Suppression (OLV/PM)
Sets the gain for internal speed feedback detection control when overvoltage suppression is active. Although this setting
rarely needs to be changed, adjustment may be necessary under the following conditions:
• Increase this setting if motor oscillation or hunting occurs when ov suppression is active.
• Decrease this setting in increments of 0.05 to decrease the drive responsiveness during ov suppression.
No. Name Setting Range Default
n8-65 Speed Feedback Detection Control Gain during ov Suppression (OLV/PM) 0.00 to 10.00 1.50
SIEP_C710616_35.book 245 ページ 2015年11月30日 月曜日 午後2時2分