36 — APC UPS cable assembly with beeper unit data sheet
Alcatel-Lucent 7342 ISAM FTTU ONT R04.05.06 July 2008 36-3
3FE 51892 AAAA TCZZA Edition 01 ONT Product Information Manual
Table 36-2 Audible alarms for cable beeper
Figure 36-2 Alarm disable push button for cable beeper
36.4 Output connections on the PowerShield
The UPS is equipped with intelligent internal diagnostics, which provide power
supply alarm signals. These signals can be monitored by the service provider so that
corrective actions can be taken. Proper escalation of alarms can dramatically
improve QoS. Table 36-3 describes the alarm connector pinouts and their associated
states.
Table 36-3 Alarm connector pinouts
36.5 Alarm descriptions
Table 36-4 describes the status alarms received from the UPS.
Alarm Description
ON BATTERY Four beeps at 1-s intervals, no repeating.
LOW BATTERY Four beeps at 1-s intervals, repeating every 5 min.
REPLACE BATTERY One 0.5-s beep, repeating every 5 min.
Alarm disable
push button
1849
4
Signal Pin number Normal state Alarm state Wire color
12 V dc 1 Red
Common 12 V dc Return 2 Black
Signal Return 3 Green
On-Battery 4 Closed Open Slate
Replace Battery 5 Closed Open Brown
Battery Missing 6 Closed Open Orange
Low Battery 7 Closed Open Blue