38 — CyberPower CyberShield CS 36 PSU/BBU unit data sheet
38-2 July 2008 Alcatel-Lucent 7342 ISAM FTTU ONT R04.05.06
ONT Product Information Manual Edition 01 3FE 51892 AAAA TCZZA
38.1 Identification
Table 38-1 provides identification information about the ONT power supply
unit/battery backup unit (PSU/BBU) from CyberPower Systems, Inc.
Table 38-1 Identification of the OPSU/BBU
38.2 Features and application notes
The PSU provides:
50 W, 47.5 to 56 V dc power supply for the BBU
input voltage range of 90 to 135 V ac at 60 Hz frequency range
surge protection of 660 joules
The BBU provides:
36 W, output voltages of 10.5 to 20 V dc while discharging, 13.1 V to 14.6 V dc
normally
commerically sealed lead-acid backup battery (12 V 7.2 Ah)
battery diagnostics, self-tests, and BBU status alarm outputs
battery and alarm control functions
The PSU/BBU meets:
UL 60950-1, CSA C22.2 No. 60950-1, NEBS Level 1 and 3 (GR1089 and
GR63), FCC Part 15 Class B
Part Number Description
3EM 22937 AA
(customer-specific logo)
3EM 22889 AA (no logo)
CyberShield CS 36 PSU 50 W, 48 V dc.
CyberShield CS 36 BBU 36 W, 12 V dc.