43 — PowerShield CP50B48 UPS unit data sheet
43-6 July 2008 Alcatel-Lucent 7342 ISAM FTTU ONT R04.05.06
ONT Product Information Manual Edition 01 3FE 51892 AAAA TCZZA
Physical description
The UPS has the following physical description:
• height: 11.60 in. (29.5 cm)
• width: 11 in. (27.9 cm)
• depth: 3.7 in. (9.4 cm)
• weight: 18.50 lb (8.41 kg)
Power
The UPS has the following input frequency/voltages:
• input frequency: 47 Hz to 63 Hz (auto sensing)
• input voltage: 87 V ac to 264 V ac
The UPS has the following output specifications:
• output voltages: –48 V dc
• output power capacity: 50 W
• maximum configurable power: 50 W
Environmental
The runtime specifications at 25°C while operating off of the battery are defined as
follows:
• load, 8 W: 24 h
• load, 15 W: 13 h
• load, 25 W: 8 h
• load, 50 W: 4 h
The operating conditions are defined as follows:
• temperature range: –4 °F to 113 °F (–20°C to 45°C)
• operating elevation: 0 to 10 000 ft above sea level (0 to 3000 m)
• storage elevation: 0 to 50 000 ft above sea level (0 to 15 000 m)
• relative humidity (non-condensing) within enclosure: 0% to 95%