42 — FlexNet FMPS-150W UPS unit data sheet
42-6 July 2008 Alcatel-Lucent 7342 ISAM FTTU ONT R04.05.06
ONT Product Information Manual Edition 01 3FE 51892 AAAA TCZZA
Two dc output and alarm connectors are provided; however, Alcatel-Lucent
recommends the use of only one dc and alarm connection per UPS for an ONT
installation. As well, Alcatel-Lucent recommends running the power wires in a
separate conduit from the alarm wires.
The UPS comes with an 8 ft line cord for connection to the main ac power supply.
The UPS can also be hard wired to the ac supply. Follow the manufacturer’s
instructions in the documentation accompanying the unit for more information about
connecting the UPS to the main ac power source.
42.8 Specifications
The following specifications apply to the UPS.
Physical description
The UPS has the following physical description:
• height: 23.75 in. (60.3 cm)
• width: 14 in. (35.6 cm)
• depth: 5.5 in. (14 cm)
• enclosure only weight: 25 lb (11.3 kg)
• weight of enclosure with both battery strings: 44.128 lb (20 kg)
Power
The UPS has the following input frequency/voltages:
• ac input frequency: 45 Hz to 66 Hz (auto sensing)
• nominal input: 90 V ac to 320 V ac
• maximum ac current draw: 2.5 A at 120 V ac (with maximum dc output, plus
charger and heater)
The UPS has the following output specifications:
• output voltage (nominal): 55 Vdc
• output power capacity: 150 W
• output current: 3.1 A typical
Environmental
The runtime specifications at 25°C using two battery strings:
• load, 30 W: 23 h
• load, 40 W: 17.22 h
• load, 50 W: 13.68 h
• load, 60 W: 11.23 h