39 — CyberPower CyberShield CS 50 UPS unit data sheet
Alcatel-Lucent 7342 ISAM FTTU ONT R04.05.06 July 2008 39-3
3FE 51892 AAAA TCZZA Edition 01 ONT Product Information Manual
Table 39-2 CyberShield CS 50 UPS LEDs for ONTs
39.5 Alarms
The UPS is equipped with intelligent internal diagnostics that provide power supply
alarm information. Open collector opto-isolators isolate the alarm signals which are
present on the power and alarm connector. The service provider can monitor these
alarm signals to isolate problems and take corrective action.
Table 39-3 describes the UPS alarm signal and output levels.
Table 39-3 Alarm signal and output levels
The UPS is also equipped with a switch, located on the back of the unit, that when
activated emits an alarm under certain conditions. If you want to enable the switch,
insert a paper clip or other object with a narrow point into the hole and press the
button.
Table 39-4 describes the function of the Buzzer On/Off switch.
Name Indicator Color Description
AC Green Operating on ac power
Yellow Operating on battery
OUTPUT Green DC output is present
BATTERY Red Battery is missing or needs replacement
Signal Description
ON BATTERY The on-battery alarm indicates that the BBU is operating
using the backup battery.
REPLACE BATTERY The replace-battery alarm indicates that the battery is
either discharged, or has failed the self test.
Replace the battery if there is a failure.
BATTERY MISSING The battery-missing alarm indicates that no battery is
detected.
LOW BATTERY The low-battery alarm indicates that the battery charge
has fallen below 45% capacity when operating from the
battery.