43 — PowerShield CP50B48 UPS unit data sheet
43-4 July 2008 Alcatel-Lucent 7342 ISAM FTTU ONT R04.05.06
ONT Product Information Manual Edition 01 3FE 51892 AAAA TCZZA
Table 43-2 LEDs
43.6 Alarms
The UPS is equipped with intelligent internal diagnostics that provide power supply
alarm information. Open collector opto-coupled transistors isolate the alarm signals,
which are present on the 7-pin power and alarm connector. The service provider can
monitor these alarm signals to isolate problems and take corrective action.
Table 43-3 describes the UPS alarms, as well as provides the output signal levels at
the power and alarm connector pins.
Table 43-3 Alarm signal and output levels
43.7 Connections
The voltage output connector at the UPS is a 3.5 mm, removable, 7-pin screw
terminal connector (ANSI: accepts 16 to 26 AWG). A 7-position Phoenix IDC
connector is used at the ONT.
Name Color Description
AC Present Green Operating on ac power
Green Flashing High-charge mode
Yellow Operating on battery
DC Output On Green DC output present
Battery Bad Red Battery missing or needs replacement
Signal Pin Description Level
ON BATT 4 The on-battery alarm indicates if the UPS
is operating using the main AC power
source or backup battery.
Low = operating from
main AC power source
Open = operating from
backup battery
REPLACE BATT 5 The replace-battery alarm indicates that
the battery is either charged, or has
failed the self test.
Replace the battery if this alarm indicates
a failure. Availability has been
compromised.
Low = battery is charged
Open = battery failed
BATT MISSING 6 The battery-missing alarm indicates
whether or not the battery is detected.
Low = battery is present
Open = battery is missing
LOW BATT 7 The low-battery alarm indicates that the
battery charge is either near full
capacity, or has fallen below 20% capacity
when operating from the battery.
Low = battery is nearly
fully charged
Open = battery charge is
below 20% capacity