41 — Delta DUPS-1232A UPS unit data sheet
Alcatel-Lucent 7342 ISAM FTTU ONT R04.05.06 July 2008 41-7
3FE 51892 AAAA TCZZA Edition 01 ONT Product Information Manual
Power
The UPS has the following input specifications:
• input frequency: 47 to 63 Hz
• input voltage: 85 to 264 V ac
• input surge protection: NEBS GR1089 section 4.7 @ 6KV
The UPS has the following output specifications:
• output voltages: 12.5 to 14.5 V dc
• output current: 2.7 A maximum
• output power: 32 W
• efficiency: > 75% with battery fully charged
• ripple: 250 mV RMS maximum
• noise: 250 mV peak-to-peak maximum
In battery backup operation mode, the UPS has the following output specifications:
• output voltages: 9.5 to 13.2 V dc
• output current: 2.7 A maximum
• output power capacity: 32 W
• efficiency at full load: > 90% with 12 V battery voltage
• ripple: 250 mV RMS maximum
• noise: 250 mV peak-to-peak maximum
Environmental
The operating conditions for the Delta DUPS-1232A UPS are:
• temperature range: –4° to 122°F (–20° to 50°C)
• relative humidity (non-condensing): 0% to 95%
The storage conditions are:
• temperature range: –4° to 122°F (–20° to 50°C)
• relative humidity (non-condensing): 0% to 95%
Note — The battery backup supports ONT operations for a minimum
of 8 h with the loading profile defined in GR-1089.