212/641 Bosch Rexroth AG | Tightening Technology 3 608 878 300
System 350 | 3 608 878 300/2019-03
The offset of the results output (ID-code + results) within the output area of the data buffer is determined
by the set number of control signals set (8 per byte).
Formats for floating decimal numbers
Measurement results and limits for torque, angle, and gradient are shown as floating decimal numbers
with a varying number of digits. The decimal character is output as a decimal point. The number of digits
before and after the decimal point is:
Table 6–9: Output area data buffer field bus for the results output of a single-channel tightening
Name relative byte address Length
[byte]
Format Unit Results output Meaning of the output
result
Control signal output 0 2 or 4 Bit – Every output signal uses 1 bit
ID code PLC
1
+ 0 max 64 ASCII – "L1234567890123" ID code as string
Channel number PLC
1
+ ID code
2
+ 0 4 ASCII – „10.4“ Rack 10, slot 4
Program no. PLC
1
+ ID code
2
+ 4 1 Int8 Program 12 0x12 = program no. 18
Step no. of the tightening
step edited last
PLC
1
+ ID code
2
+ 5 3 ASCII – "03A" Step 3A
Quality code PLC
1
+ ID code
2
+ 8 5 ASCII – „00001“ Quality code 1 = all OK
End torque
3
PLC
1
+ ID code
2
+ 13 4 Int32 0,00001 Nm d0 1b 50 d0 0x00501bd0
= 5250000 × 0,00001 Nm
=52,5Nm
End angle
3
PLC
1
+ ID code
2
+ 17 4 Int32 0.0001° 08 02 37 00 0x00370208
= 3605000 × 0,0001°
= 360,5 °
Max. limit torque
3
PLC
1
+ ID code
2
+ 21 4 Int32 0,00001 Nm ffffffff 0xffffffff = –1 (not valid)
Min. limit torque
3
PLC
1
+ ID code
2
+ 25 4 Int32 0,00001 Nm d0 1b 50 d0 0x00501bd0
= 5250000 × 0,00001 Nm
=52,5Nm
Max. limit angle
3
PLC
1
+ ID code
2
+ 29 4 Int32 0.0001° ffffffff 0xffffffff = –1 (not valid)
Min. limit angle
3
PLC
1
+ ID code
2
+ 33 4 Int32 0.0001° 08 02 37 00 0x00370208
= 3605000 × 0,0001°
= 360,5 °
1 Storage area for output control signals (PLC = programmable logic control)
2 Agreed length for the ID code
3 Values that are not recorded are output as –1 (0xffffffff).
The number and order of the result values is fixed. The output of parameters and/or step results of docu
steps is not possible.
XML and IPM output of torque values is always with two decimals.
Table 6–10: Number of digits before and after the decimal point for measurement values
Measurement/limit value Number
Integer parts
Number
Decimal points
Torque T
MaxSpindle
< 10 Nm 1 3
T
MaxSpindle
< 100 Nm 2 2
T
MaxSpindle
< 1,000 Nm 3 1
T
MaxSpindle
1,000 Nm 4 0 (no decimal!)
Gradient T
MaxSpindle
< 10 Nm 0 4
T
MaxSpindle
< 100 Nm 1 3
T
MaxSpindle
< 1,000 Nm 2 2
T
MaxSpindle
1,000 Nm 3 1