3 608 878 300 Tightening Technology | Bosch Rexroth AG 533/641
System 350 | 3 608 878 300/2019-03
Fig. 7–8: X1N4 voltage selection terminals with connection groups G1, G2, and G3
NOTICE
Varying assignment of connections within a group
Device destruction
Only the connections of one group may be used.
Do not simultaneously assign varying groups.
NOTICE
Incorrect wiring
Damages to the control and power electronics
Always feed the mains connection through the upper terminal strip (see Table 7–5)
The lower terminal strip must remain fully wired.
Table 7–5: Voltage selection terminals
Pin Signal Description Voltage/current
1 PE PE wire PE potential
G1 2 L1 L1 mains connection 380 V~ – 415 V~ / 4.6 A
3 L2 L2 mains connection 380 V~ – 415 V~ / 4.6 A
4 L3 L3 mains connection 380 V~ – 415 V~ / 4.6 A
G2 5 L1 L1 mains connection 440 V~ – 480 V~ / 3.9 A
6 L2 L2 mains connection 440 V~ – 480 V~ / 3.9 A
7 L3 L3 mains connection 440 V~ – 480 V~ / 3.9 A
G3 8 L1 L1 mains connection 500 V~ / 3.5 A
9 L2 L2 mains connection 500 V~ / 3.5 A
10 L3 L3 mains connection 500 V~ / 3.5 A
G4 11 L1 L1 device connection 230 V~ / 7.5 A
12 L2 L2 device connection 230 V~ / 7.5 A
13 L3 L3 device connection 230 V~ / 7.5 A
}
.1
.2
.1
.2
.1
.2
.3
.4
1
.1
.2
.1
.2
.1
.2
.1
.2
.1
.2
.1
.2
.1
.2
234 567 8 910
.1
.2
.1
.2
.1
.2
11 12 13
G1 G2 G3 G4
Terminal strips for mains connection Device connection