3 608 878 300 Tightening Technology | Bosch Rexroth AG 571/641
System 350 | 3 608 878 300/2019-03
Configuration settings in the "RSLogix 5000" software for IMenip
Configuration of the IMenip interface module (EtherNet/IP) in the "RSLogix 5000" software of the
company Rockwell is realized using the following parameters:
• General parameters
– Superior instance: X_1788_ENBT
– Name: IMenip
• Connection parameter input (32 bit):
– Assembly instance: 100
–Size: 1
Ensure that in the PLC partner control of the company Rockwell, you adjust the value of this
parameter of the configuration of the IMenip interface module. In order to ensure smooth
communication, the following parameters must in this case correspond to each other:
– Connection parameter input size in the "RSLogix 5000"
– Configured ranges O points + send in the BS350
Generally, the following applies:
Connection parameter input size=configured ranges O points + send
• Connection parameter output (32 bit):
– Assembly instance: 150
–Size: 1
Ensure that in the PLC partner control of the company Rockwell, you adjust the value of this
parameter of the configuration of the IMenip interface module. In order to ensure smooth
communication, the following parameters must in this case correspond to each other:
– Connection parameter output size in the "RSLogix 5000"
– Configured ranges I points + receive in the BS350
Generally, the following applies:
Connection parameter output size=configured ranges I points + receive
• Connection parameter configuration (8 bit):
– Assembly instance: 1
–Size: 0
Examples of the configuration of the connection parameters input size and output size in the
"RSLogix 5000" software:
• If the parameter Configured ranges O points + send is set to the value 256 bytes, the
connection parameter Input size must be set to the following values, depending on the
communication format:
– Communication format SINT (8 bit per size): 256
– Communication format INT (16 bit per size): 128
– Communication format DINT (32 bit per size
): 64
• If the parameter Configured ranges I points+receive is set to the value 256 bytes, the
connection parameter output size must be set to the following values, depending on the
communication format:
– Communication format SINT (8 bit per size): 256
– Communication format INT (16 bit per size): 128
Communication format DINT (32 bit per size): 64
The software "RSLogix 5000" of the company Rockwell is not able to read the EDS file of the Tightening
System 350. For this reason, the IMenip interface module (EtherNet/IP) must be set up as general
Ethernet module (type: ETHERNET MODULE | Description: General Ethernet modules). Detailed
information on the correct configuration is contained in section „Configuration settings in the "RSLogix
5000" software for IMenip“ on page 571.