600/641 Bosch Rexroth AG | Tightening Technology 3 608 878 300
System 350 | 3 608 878 300/2019-03
IMmtcp This parameter dialog consists of two index cards that can be selected in the Set ModbusTCP interface
group:
• I/O and data
• Configuration
Index card: I/O and data
No settings can be made in the Configured ranges field: The grayed out fields cannot be edited. The
parameters displayed in this field depend on the selected number of I/O points.
Index card: Configuration
The following settings can be made in this index card:
• Get configuration via DHCP
or
• Use the following configuration: If you select this item, you can enter the following parameters:
– IP address: Assigned by the network administrator; identifies the participant in the data exchange
– Subnet mask: Assigned by the network administrator; contains information on the network
configuration (address range)
– Gateway: Establishes the external connection
• Host name: Name by which the Ethernet participant (here the KE of the tightening system) can be
addressed.
Table 7–32: Settings in BS350 for IMmtcp - I/O and data
Element Description
Number of I points Number of control signals to be processed via the ModbusTCP interface. Value
range 16 to 512 input signals (2 to 64 bytes)
Number of O points Number of control signals to be processed via the ModbusTCP interface. Value
range 16 to 512 output signals (2 to 64 bytes)
Receive data Memory location for receiving the ID code, max. 254 bytes at 2 bytes for I points
Send data Memory location for sending results, max. 254 bytes at 2 bytes for O points
Receive IL data Memory location for receiving IL data, max. 254 bytes at 2 bytes for I points
These data are processed using the IL function block ControlFieldbus.
Send IL data Memory location for sending of IL data, max. 254 bytes at 2 bytes for O points
These data are processed using the IL function block ControlFieldbus.