User Manual Section 3
GFK-2958L May 2021
Configuration 42
2 Channel High
Speed Counter,
AB 100 kHz
disabled (0) /
enabled (1)
Ch 0 ... Ch 1: Filter time
signal A
0.01ms [100 kHz] (0) /
0.017ms [50 kHz] (1) /
0.033ms [30 kHz] (2) /
0.1ms [10 kHz] (3) /
0.2ms [5 kHz] (4) /
0.5ms [2 kHz] (5) /
1ms [1 kHz] (6)
Ch 0 ... Ch 1: Filter time
signal B
0.01ms [100 kHz] (0) /
0.017ms [50 kHz] (1) /
0.033ms [30 kHz] (2) /
0.1ms [10 kHz] (3) /
0.2ms [5 kHz] (4) /
0.5ms [2 kHz] (5) /
1ms [1 kHz] (6)
Ch 0 ... Ch 1: Process alarm
overflow
disabled (0) /
enabled (1)
Ch 0 ... Ch 1: Process alarm
underflow
disabled (0) /
enabled (1)
Ch 0 ... Ch 1: Process alarm
comp. value
disabled (0) /
enabled (1)
Ch 0 ... Ch 1: Process alarm
end value
disabled (0) /
enabled (1)
Ch 0 ... Ch 1: Counting
mode
count endless (0) /
on–e - –orward (1) /
on–e - –ackwards (2) /
on–e - –o main direction (3) /
periodic forward (4) /
periodic backwards (5)/
periodic – no main direction (6)
Ch 0 ... Ch 1: Comparison
function
disabled (0) /
higher equal comparison value
(1) /
lower equal comparison value
(2)/
equal comp value (3)
Ch 0 ... Ch 1: Counter dir.
signal B inv.
disabled (0) /
enabled (1)
Ch 0 ... Ch 1: Signal mode
Rotary transduc–r - –ingle (0) /
Rotary transduc–r - –ouble (1) /
Rotary transduc–r - –uadruple
(2) /
Pulse and Direction (3)/
disabled (4)
Ch 0 ... Ch 1: Counter
behavior internal gate
Interrupt counting (0) /
Cancel counting (1)
Ch 0 ... Ch 1:
Load value
Ch 0 ... Ch 1: Hysteresis