3.4 Programming Mode
3-16
3.4 Programming Mode
The Programming mode provides you with the following functions--setting and checking function code data,
monitoring maintenance information and checking input/output (I/O) signal status. The functions can be easily
selected with the menu-driven system. Table 3.4-1 lists menus available in Programming mode. The leftmost digit
(numerals) of each letter string on the LED monitor indicates the corresponding menu number and the remaining
three digits indicate the menu contents.
When the inverter enters Programming mode from the second time on, the menu selected last in Programming
mode will be displayed.
Table 3.4-1 Menus Available in Programming Mode
Menu # Menu
LED monitor
shows:
Main functions Refer to:
1 Data Setting
!f__
F codes (Fundamental functions)
Selecting each of
these function
codes enables its
data to be
displayed/
changed.
Section
3.4.1
!e__
E codes (Extension terminal functions)
!c__
C codes (Control functions)
!p__
P codes (Motor 1 parameters)
!h__
H codes (High performance functions)
!h1_
H1 codes (100s)
(High performance functions)
!a__
A codes (Motor 2 parameters)
!j__
J codes (Application functions 1)
!j1_
J1 codes (100s) (PID functions)
!d__
d codes (Application functions 2)
!u__
U codes (Customizable logic functions)
!u1_
U1 codes (100s)
(Customizable logic functions)
!y__
y codes (Link functions)
!k__
K code (Keypad functions)
!o__
o codes (Optional functions) (Note)
2
Data
Checking
"rep
Displays only function codes that have been changed from
their factory defaults. You can refer to or change those
function code data.
Section
3.4.2
3
Drive
Monitoring
#ope
Displays the running information required for maintenance
or test running.
Section
3.4.3
4 I/O Checking
$i_o
Displays external interface information.
Section
3.4.4
5
Maintenance
Information
%che
Displays maintenance information including cumulative run
time.
Section
3.4.5
6
“Alarm
Information
&al
Displays the recent four alarm codes. You can refer to the
running information at the time when the alarm occurred.
Section
3.4.6
7 Data Copying
'cpy
Allows you to read or write function code data, as well as
verifying it. (Only available with TP-E1U)
Section
3.4.7
8 Destination
(des
Setting the shipping destination region.
Section
4.4
0 Quick Setup
*fnc
Displays only basic function codes to customize the inverter
operation.
Section
3.4.8
(Note) The “o” codes are displayed only when the corresponding option is mounted. For details, refer to the