5.2 Function Codes Table
5-2
5.2 Function Codes Table
5.2.1 Supplementary note
Change, reflect, and save function code data during operation
Function codes are categorized into those which data change is enabled during operation of the inverter and those
which such change is disabled. The meaning of the code in the Change during operationcolumn of the function
code table is described in the following table.
Code
Change during
operation
Reflect and save data
Y* Allowed
At the point when data is changed by / key, the changed data is immediately
reflected on the operation of inverter. However, at this stage, the changed value is
not saved to the inverter. In order to save it to the inverter, press key. Without
saving by key and leaving the state of when the change was made by the
key, the data before the change is reflected on the operation of inverter.
Y Allowed
Even if data is changed by the / key, the changed data will not be reflected
on the operation of the inverter as is; by pressing the key, the changed value
is reflected on the operation of the inverter and is also saved to the inverter.
N Not allowed
Copying data
Function code data can be copied collectively by using the optional keypad TP-E1U (program mode menu
number 7 Data copy). By using this function, it is possible to read out all function code data and write the same
data to a different inverter.
However, if the specification of inverter at the copy source and copy destination is not identical, some function
codes may not be copied due to security reason. According to necessity, configure the settings individually for the
function codes that are not copied. The behaviour of the function codes regarding data copy is indicated in the
data copycolumn in the function code table in the next page and following.
Y: to be copied.
Y1: When inverter capacity is different, copying will not be performed.
Y2: When voltage group is different, copying will not be performed.
N: not to be copied.
Negative logic setting of data
Digital input terminal and transistor/contact output terminal can become a signal for which negative logic is
specified by function code data setting. Negative logic is a function to reverse ON and OFF state of input or output,
and switch Active ON (function enabled with ON: positive logic) and Active OFF (function enabled with OFF:
negative logic). However, negative logic may not be enabled depending on the function of the signal.
Negative logic signal can be switched by setting the data with 1000 added to the function code data of the function
to be set. For example, the following example shows when coast to a stop command “BX” is selected by function
code E01.
Function code data Action
7 “BX” is ON and coast to a stop (Active ON)
1007 “BX” is OFF and coast to a stop (Active OFF)