[ 2 ] Compliance with the low voltage directive in the EU
General-purpose inverters are regulated by the Low Voltage Directive in the EU. Fuji Electric states that all our
inverters with CE marking are compliant with the Low Voltage Directive.
■ Note
If installed according to the guidelines given below, inverters marked with CE are considered as compliant with the
Low Voltage Directive 2006/95/EC.
Compliance with European Standards
Adjustable speed electrical power drive systems.
Part 5-1: Safety requirements. Electrical, thermal and energy. IEC/EN61800-5-1 : 2007
residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB)* as the sole method
of electric shock protection. Be sure to use ground wires whose size is greater than power supply lines.
*With overcurrent protection.
2. To prevent the risk of hazardous accidents that could be caused by damage of the inverter, install the
specified fuses in the supply side (primary side) according to the following tables.
• Breaking capacity: Min. 10 kA • Rated voltage: Min. 500 V
Power supply
voltage
Nominal applied motor
(kW)
Inverter type
HHD/HND/HD/
ND mode
Fuse rating
(A)
Three phase
200V
0.1
FRN0001E2■-2
HHD 6(IEC60269-2)
0.2 HND 6(IEC60269-2)
0.2
FRN0002E2■-2
HHD 6(IEC60269-2)
0.4 HND 6(IEC60269-2)
0.4
FRN0004E2■-2
HHD 10(IEC60269-2)
0.75 HND 10(IEC60269-2)
0.75
FRN0006E2■-2
HHD 15(IEC60269-2)
1.5 HND 15(IEC60269-2)
1.5
FRN0010E2■-2
HHD 20(IEC60269-2)
2.2 HND 20(IEC60269-2)
2.2
FRN0012E2■-2
HHD 30(IEC60269-2)
3.0 ND 30(IEC60269-2)
3.7
FRN0020E2■-2
HHD 40(IEC60269-2)
5.5 ND 50(IEC60269-2)
5.5
FRN0030E2■-2
HHD 125(IEC60269-4)
7.5 HND 125(IEC60269-4)
7.5
FRN0040E2■-2
HHD 160(IEC60269-4)
11 HND 160(IEC60269-4)
11
FRN0056E2■-2
HHD 160(IEC60269-4)
15 HND 160(IEC60269-4)
15
FRN0069E2■-2
HHD 200(IEC60269-4)
18.5 HND 200(IEC60269-4)
18.5
FRN0088E2■-2
HHD 250(IEC60269-4)
22 HND 250(IEC60269-4)
22
FRN0115E2■-2
HHD 350(IEC60269-4)
30 HND 350(IEC60269-4)