11.9 Power Regenerative PWM Converters, RHC Series
11-36
11.9.3 Function specifications
■ Terminal functions
Classifi
-cation
Symbol Name Functions
Main circuit
L1/R, L2/S, L3/T
Main circuit power
inputs
Connects with the three-phase input power lines through a dedicated
reactor.
Connects with the power input terminals P(+) and N(-) on an inverter.
Grounding terminal for the converter’s chassis (or enclosure).
Auxiliary power input for
For the backup of the control circuit power supply, connect the power lines
same as that of the main power input.
Voltage
detection
R1, S1, T1
Voltage detection terminals for the internal control of the converter. Connect
with the power supply side of the dedicated reactor or filter.
R2, T2
monitoring
Detection terminal for AC fuse blown.
Input signal
[RUN] Run command
Short-circuiting terminals [RUN] and [CM] runs the converter; opening them
stops the converter.
[RST] Reset alarm command
When the converter stops due to an alarm, removing the alarm factor and
short-circuiting the terminals [RST] and [CM] cancels the protective
function, restarting the converter.
[X1]
General-purpose
transistor input
0: Enable external alarm trip THR
1: Cancel current limiter LMT-CCL
2: 73 answerback 73ANS
3: Switch current limiter I-LIM
Common terminal for digital input signals.
Connects to PLC output signal power supply. (Rated voltage: 24 VDC (22 to
27 VDC)
Output signal
[30A/B/C]
Alarm relay output
(for any alarm)
Outputs a signal when the protective function is activated to stop the
converter.
(Contact: [1C], Terminals [30A] and [30C] are closed: Signal ON) (Contact
rating: 250 VAC, max. 50 mA)
[Y1], [Y2], [Y3],
[Y11] to [Y18]
General-purpose
transistor output
1: Converter ready to run RDY
2: Power supply current limiting IL
3: Lifetime alarm LIFE
4: Heat sink overheat early warning PRE-OH
5: Overload early warning PRE-OL
6: Power running DRV
7: Regenerating REG
8: Current limiting early warning CUR
9: Restarting after momentary power failure U-RES
10: Synchronizing power supply frequency SY-HZ
11: Alarm content 1 AL1
12: Alarm content 2 AL2
13: Alarm content 4 AL4
14: Option DO OPT-DO
* Mounting the OPC-VG7-DIOA option makes 8 points of DO extended
functions available. (DI functions are not available.)
[Y5A/C] Relay output
[A01], [A04],
[A05]
General-purpose
analog output
1: Input current in RMS I-AC
2: Input voltage in RMS V-AC
3: DC link bus voltage V-DC
4: Power supply frequency FREQ
5: +10 V test P10
6: -10 V test N10
* Mounting the OPC-VG7-AIO option makes 2 points of AO extended
functions available. (AI functions are not available.)
Common terminal for analog output signal.
relay outputs
Control output for the input relay of the external charging resistor (73).